100 kVA

This 100 kVA generator is a powerhorse of performance for your industry. It will require very low maintenance and is compliant with the latest CPCB II emission norms.
DutyPrime
Controller TypeDSE
Starting System12V D.C.
Weight (Kg) (Approx.)1850
Noise @75% load (dBA)<75Db @ 1m
Dimension (LxWxH)(mm) (with duct)3150X1100X2040
Dimension (LxWxH)(Feet)(with duct)10.3X3.6X6.7
Battery Type12 Volt
Battery output (mAH)130 or more
Battery MakeExide Genplus or Amaron
Silencer Dia. (mm)350
Exhaust Pipe Dia. (Inch)4
Base Body Type/Thickness(mm)Sheet/3&4
Body Sheet Thickness (mm)1.2
PU Foam Thickness (mm)40
Fuel Tank Capacity (Liters)180
Model697TC52
MakeTATA MOTORS LIMITED
Speed(RPM)1500
Cubic Capacity (L)5.675
BHP (gross)93.5
No. of Cylinders6, in-line
Bore (mm)97
Stroke (mm)128
Compression Ratio17.5:01
AspirationTCIC
Cooling SystemLiquid Cooled
GoverningElectronic, Class A0
Fuel TypeHSD
Oil Capacity (L)16
Oil GradeCI4 or +
Lube oil change period500 hours/6 Month
Current at 100% (A)108/35
Make & TypeDeepsea or equivalent
No. of BearingsSingle
Class of InsulationH
Voltage Variation (%)+/- 1%
Enclosure ConfirmationIP23
Phase1/3
Coupling DetailsSAE2/10
Voltage (V)230/415
Frequency (Hz)50
Power Factor0.8
Maximum unbalanced load across phasesLess than or equal to 25%
MakeDeepsea or equivalent
Sheet typeCRCA
Sheet thickness (mm)1.6
MCB/MCCBMCB/MCCB
Pole/ Rating 1Phase (Amps.)2 Pole / 125 Amp
Pole Rating 3 Phase (Amps.)3 Pole / 32 Amp
Conductors suitable capacity of incoming and outgoing terminalsYes
Indicating lamps for "Load ON" and "DG Set Running"Yes
MCB/MCCB with overload and short circuit protectionYes
Shutdown for O/U Voltage, Overload, O/U Hz, Battery Charging failure, Belt Break, Emergency Stop, Low Fuel, Radiator water level, HWT, LLOPYes
Display for Voltage Phase-Nutral, Frequency, Current Oil Pressure, Water Temp., RMP, Running Hrs, Service Due Hrs, Battery Volt., Fuel Level in %Yes
LED & Alarm for O/U Voltage, Overload, O/U Hz, Battery Charging failure, Belt Break, Emergency Stop, Low Fuel, Service Due, Radiator Water Level, HWT & LLOPYes